Condensate discharge run externally without protection

    What it looks like

    Boiler lockout in the first hard frost of the winter, usually across a number of plots on the same site at once.

    Why it happens

    Condensate pipe taken outside in small-bore plastic and run a long distance to a gully, without insulation or the required fall.

    What it costs if it is missed

    Nuisance boiler failures after handover, customer care visits across the site, and avoidable reputational damage in the first heating season.

    How to inspect for it

    Trace the condensate run at second fix: internal termination preferred, external runs kept short, in a larger bore, insulated and falling continuously to the discharge point.

    How to prevent it

    Design the condensate route at first fix with the heating layout instead of leaving it to the commissioning engineer.

    Basis in regulation