    Plasterboard fixing and fire resistance

    300 mm

    Plasterboard must be fixed to light steel studs with self-drilling, self-tapping screws at specified centres, typically a maximum of 300mm

    Plasterboard must be fixed to light steel studs with self-drilling, self-tapping screws at specified centres, typically a maximum of 300mm. Where fire resistance is a requirement, the plasterboard must demonstrate adequate performance and comply with BS EN 520. Minimum plasterboard thicknesses are specified based on stud spacing: 9.5mm for up to 450mm spacing and 12.5mm for up to 600mm spacing.

    Basis in regulation

    How to check it on site

    Check plasterboard thickness, screw spacing, and ensure fire-rated boards are used in required locations as per design specifications.

    Common failure

    Incorrect screw spacing or using plasterboard of insufficient thickness can compromise the fire resistance and structural integrity of the wall lining, potentially leading to cracking or collapse.

    Last updated 23 August 2026. This is our editorial summary of publicly available regulation, not building control approval or a warranty determination.