Minimum
    England

    Minimum masonry thickness around a flue

    100 mm around the flue; 200 mm between flues serving different dwellings

    Masonry chimneys built with a suitable liner.

    The masonry around a flue, excluding the liner, should be at least 100 mm thick. Where a flue passes beside a flue serving another dwelling, at least 200 mm of solid masonry should separate the two.

    Basis in regulation

    How to check it on site

    Measure the wall thickness at the chimney breast before plastering, and check the liners are the right way up with sockets uppermost.

    Common failure

    Chimney cheeks built in half brick with a liner squeezed in, leaving less than 100 mm of masonry around the flue.

    Last updated 23 August 2026. This is our editorial summary of publicly available regulation, not building control approval or a warranty determination.