    Equivalent ventilation areas for a cold roof

    10,000 mm²/m at pitched eaves; 25,000 mm²/m at low level on flat or shallow roofs; 5,000 mm²/m at the ridge

    Cold roof construction with the insulation at ceiling or deck level.

    Every figure for this topic is on one page: Roof void ventilation, access and fire compartmentation

    Read the full answer

    Cold roof ventilation is specified as an equivalent free area per metre run: 10,000 mm² at the eaves of a pitched roof of 15 degrees or steeper, 25,000 mm² at low level where the roof is flat or pitched below 15 degrees, and 5,000 mm² at high level where ridge ventilation is used.

    Basis in regulation

    How to check it on site

    Compare the ventilator product data sheet against the required equivalent area — a vent's physical size is not its equivalent area.

    Common failure

    Vents chosen on physical opening size, delivering a fraction of the equivalent area the roof needs.

    Last updated 23 August 2026. This is our editorial summary of publicly available regulation, not building control approval or a warranty determination.