Separation between a flue and combustible material
200 mm from the flue face, or 40 mm from the outer face of the masonry
Masonry chimneys and fireplace recesses serving combustion appliances.
Combustible material should be kept at least 200 mm away from the inside surface of a flue, or at least 40 mm from the outer surface of a masonry chimney or fireplace recess.
Basis in regulation
How to check it on site
Check joist trimming, floor decking and skirting runs around the chimney breast before the trimming is boarded over.
Common failure
Joist ends or timber grounds built hard against the chimney breast where nobody can see them once the floor is down.
Last updated 23 August 2026. This is our editorial summary of publicly available regulation, not building control approval or a warranty determination.