Minimum
    England

    Hybrid roof ventilation with air permeable coverings

    25 mm

    the presence and continuity of the 25mm clear air gap, the specified eaves and ridge ventilation, and the correct installation of the AVCL.

    Every figure for this topic is on one page: Roof void ventilation, access and fire compartmentation

    Read the full answer

    Hybrid roof designs, such as room-in-roof spaces, which incorporate an air permeable outer covering and HR type underlay, require specific ventilation measures to ensure moisture control. A continuous clear airway of at least 25mm should be maintained, with corresponding eaves ventilation of 25,000mm²/m and ridge ventilation of 5,000mm²/m. Additionally, an Air and Vapour Control Layer (AVCL) is essential on the warm side of the insulation.

    Basis in regulation

    How to check it on site

    Verify the presence and continuity of the 25mm clear air gap, the specified eaves and ridge ventilation, and the correct installation of the AVCL.

    Common failure

    Obstruction of the ventilation pathway by insulation or sarking boards, or gaps in the AVCL leading to interstitial condensation.

    Last updated 28 August 2026. This is our editorial summary of publicly available regulation, not building control approval or a warranty determination.