Minimum
England
Roof underlay horizontal lap
100 mm at pitches of 15° and above; 150 mm below 15°, and at least 150 mm where the underlay is unsupported
Pitched roof underlay beneath tiles or slates
The minimum overlap between successive courses of roofing underlay.
Basis in regulation
How to check it on site
Check laps before battening starts. Confirm the underlay drapes into the gutter over an eaves carrier rather than stopping short behind the fascia.
Common failure
Underlay finishing behind the fascia so water discharges into the soffit instead of the gutter.
Effective from 20 August 2026. Last updated 23 August 2026. This is our editorial summary of publicly available regulation, not building control approval or a warranty determination.