    Ductwork Fixing and Condensate Management

    750 mm

    MVHR ductwork must be securely fixed at appropriate intervals to prevent sagging, typically no more than 750mm apart, or as per manufacturer guidelines

    MVHR ductwork must be securely fixed at appropriate intervals to prevent sagging, typically no more than 750mm apart, or as per manufacturer guidelines. Horizontal duct runs should be installed to a slight fall towards a condensate outfall to prevent water accumulation, while external wall penetrations must slope downwards to prevent water ingress. Ductwork should also be isolated from building elements to minimise noise transfer.

    Basis in regulation

    How to check it on site

    Verify ductwork is securely fixed at correct intervals, horizontal runs fall correctly for drainage, and penetrations slope outwards; check for isolation from surfaces.

    Common failure

    Insufficient fixing causes sagging, leading to condensate traps and air pressure loss, while direct contact with surfaces can transmit noise.

    Last updated 23 August 2026. This is our editorial summary of publicly available regulation, not building control approval or a warranty determination.