Maximum
    England

    Wall tie spacing at reveals and movement joints

    Additional ties at 300 mm vertical centres within 225 mm of the opening

    Within 225 mm of an unbonded vertical edge — reveals, movement joints, wall ends

    Every figure for this topic is on one page: Wall tie spacing: how far apart should cavity wall ties be?

    Read the full answer

    Additional ties required within a short distance of an unbonded edge, such as a window or door reveal.

    Wall ties at 900mm horizontal and 450mm vertical centres, staggered900 max horizontal450elevation — ties staggered row to row
    Standard field spacing shown for comparison — ties tighten to 300mm vertical centres within 225mm of a reveal or movement joint.Original ProPlot drawing, not to scale. Geometry verified against Approved Document A, structure.

    Basis in regulation

    How to check it on site

    Check every reveal on each lift. Ties should be visible in the perp adjacent to the closer before insulation and cavity closers are fitted.

    Common failure

    Standard field spacing carried straight past a reveal, leaving the free edge of the outer leaf unrestrained.

    Effective from 20 August 2026. Last updated 23 August 2026. This is our editorial summary of publicly available regulation, not building control approval or a warranty determination.