Minimum
    England

    Low-Level Protection for Timber Frame and SIPs

    150 mm

    For closed panel timber frame and structural insulated panels (SIPs), the lowest timber element must be positioned at a minimum of 150mm above the finished ground level

    Every figure for this topic is on one page: Timber frame stud spacing, sheathing and restraint straps

    Read the full answer

    For closed panel timber frame and structural insulated panels (SIPs), the lowest timber element must be positioned at a minimum of 150mm above the finished ground level. This height can be reduced to 75mm where the site has good drainage and low water table conditions. Damp-proof courses (DPCs) are essential beneath all sole plates of external walls and internal partitions to prevent moisture migration from the ground.

    Basis in regulation

    How to check it on site

    Check that the lowest timber members are at the correct height above finished ground level and DPCs are correctly installed beneath sole plates.

    Common failure

    Insufficient clearance from ground level or missing/defective DPCs can lead to dampness and rot in timber elements.

    Last updated 23 August 2026. This is our editorial summary of publicly available regulation, not building control approval or a warranty determination.