Minimum
    England

    Fire stopping at a service penetration

    Reinstate the full fire resistance of the element

    Sealed with a system tested for that substrate, aperture size and service type

    Every figure for this topic is on one page: Cavity barriers and fire stopping around openings and services

    Read the full answer

    A penetration must be sealed back to the fire resistance of the element it passes through — the seal is only as good as the tested system it belongs to.

    Basis in regulation

    How to check it on site

    Record the product, batch and installer for each penetration; unlabelled foam is not evidence.

    Common failure

    Gap-filling foam used as a fire stop, which has no fire rating on its own.

    Effective from 22 August 2026. Last updated 23 August 2026. This is our editorial summary of publicly available regulation, not building control approval or a warranty determination.